Wire Runs and Voltage Loss
|
2% Voltage Drop Guidelines 12 volts Do not exceed 2% for wire runs. A 5% loss is ok on lighting circuits in some cases, butthe next larger wire size cost is usually small and dramatically increases efficiency of batteries. |
||||||||||
| Amps | #14 | #12 | #10 | #8 | #6 | #4 | #2 | #1/0 | #2/0 | #4/0 |
| 1 | 45 | 70 | 115 | 180 | 290 | 456 | 720 | . | . | . |
| 2 | 22.5 | 35 | 57.5 | 90 | 145 | 228 | 360 | 580 | 720 | 1060 |
| 4 | 10 | 17.5 | 27.5 | 45 | 72.5 | 114 | 180 | 290 | 360 | 580 |
| 6 | 7.5 | 12 | 17.5 | 30 | 47.5 | 75 | 120 | 193 | 243 | 380 |
| 8 | 5.5 | 8.5 | 11.5 | 22.5 | 35.5 | 57 | 90 | 145 | 180 | 290 |
| 10 | 4.5 | 7 | 11.5 | 18 | 28.5 | 45.5 | 72.5 | 115 | 145 | 230 |
| 15 | 3 | 4.5 | 7 | 12 | 19 | 30 | 48 | 76.5 | 96 | 150 |
| 20 | 2 | 3.5 | 5.5 | 9 | 14.5 | 22.5 | 36 | 57.5 | 72.5 | 116 |
| 25 | 1.8 | 2.8 | 4.5 | 7 | 11.5 | 18 | 29 | 46 | 58 | 92 |
| 30 | 1.5 | 2.4 | 3.5 | 6 | 9.5 | 15 | 24 | 38.5 | 48.5 | 77 |
| 40 | . | . | 2.8 | 4.5 | 7 | 11.5 | 18 | 29 | 36 | 56 |
| 50 | . | . | 2.3 | 3.6 | 5.5 | 9 | 14.5 | 23 | 29 | 46 |
| 100 | . | . | . | . | 2.9 | 4.6 | 7.2 | 11.5 | 14.5 | 23 |
| 150 | . | . | . | . | . | . | 4.8 | 7.7 | 9.7 | 15 |
| 200 | . | . | . | . | . | . | 3.6 | 5.8 | 7.3 | 11 |
TO SOLVE VOLTAGE DROP PROBLEMSCONSIDER A HIGH VOLTAGE GEN AND BLADE!
WindGenSuperStore.Com
has larger high voltage generators; great for long wire runs and
we have bullet proof all weather gens -
CHEAP!
Check the current specials, we no longer
sell on ebay (due to fees) so you'll need to find
specials at our
online store.
We provide fine airfoils and you'll be getting the LOWEST
COST PER AMP in wind generators |
5% Voltage Drop Table
120v and 24v
Five percent is acceptable in most low voltage
systems, except 12 volt (see above). NOTE: To obtain a 2% figure
from these tables, divide the given distance shown in the table by 2.5.
For calculating distances for 48 volt systems, multiply the 24 volt
distances by 2.
For 240 volt systems, multiply the 120 volt distances by 2.
Below stepped lines check ampacity. The (=) indicates over 1000 feet.
Top table = 120/240 volts; Lower table
= 24/48 volts;
or slide page to view voltage -------------------->
Below stepped lines check ampacity. The (=) indicates over 1000 feet.
**IMPORTANT**
Before using these tables, some calculations must first be performed by the system designer to insure accurate current ratings and safety factors are used. For solar modules, the UL-1703 standard requires the short circuit current (lsc) rating be multiplied by 125% before other factors are applied. This is because the electrical performance can increase above the factory rating due to the increased operating temperatures and enhanced irradiances over 1000W/M2 (such as edge-of-cloud effect).
|
|
The NEC requires the short circuit current ratings of the PV module or array be multiplied by 125% before calculating ampacities of any cable or overcurrent device. This is in addition to the UL rquired 125%! This yields a multiplier of (125%x125%=156%) or 1.56. Although this may seem redundant, good design practice dictates both factors should be used when determining wire size from the solar array to the battery.
For larger batteries and inverters (battery to inverter cable
connections)
a minimum 4/0 cable is recommended.
| Maximum Ampacity for Copper and Aluminum Wire | ||
| Wire Size | Copper | Aluminum |
| 14 | 25 | . |
| 12 | 30 | 25 |
| 10 | 40 | 35 |
| 8 | 55 | 45 |
| 6 | 75 | 60 |
| 4 | 95 | 75 |
| 2 | 130 | 100 |
| 1 | 150 | 115 |
| 1/0 | 170 | 135 |
| 2/0 | 265 | 150 |
| 4/0 | 360 | 205 |
NEC allows rounding up cable ampacity to next standard fuse or breaker.